Title :
For a successful ASD installation . . .look beyond the electronics
Author_Institution :
Wisconsin Electr. Power Co., Milwaukee, WI, USA
Abstract :
Electrical and mechanical design of drive components must suit wiring practices based on recognized industry standards. Safety grounding, medium voltage cable termination, cable training, and electrical clearances are discussed using power plant fan installations in a particular power plant as a case study. The design shortcomings found during the installation of several large 4 kV drives and the corrective actions taken (including the revision of specifications for later drive projects) are explained
Keywords :
earthing; electric connectors; installation; safety; variable speed drives; 4 kV; MV cable termination; adjustable speed drives; cable training; electrical clearances; electrical design; industry standards; mechanical design; power plant fan installations; safety grounding; wiring practices; Electrical safety; Frequency; Grounding; Inverters; Medium voltage; Power cables; Power generation; Power system planning; Synchronous motors; Variable speed drives;
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 1991. Conference Record. Papers presented at the 1991 Annual Meeting
Conference_Location :
Memphis, TN
Print_ISBN :
0-7803-0021-1
DOI :
10.1109/ICPS.1991.153065