Title :
Distortion of phase resolved partial discharge pattern due to harmonics and saturation
Author :
Gross, Detlev W. ; Fruth, Bernhard A.
Author_Institution :
Power Diagnostix Syst. GmbH, Aachen, Germany
Abstract :
Field measurements on high voltage apparatus, such as voltage transformers (VT) as well as tests on gas insulated switchgear (GIS) powered on site by VTs showed up power frequency harmonics and/or distortions of the AC shape due to core saturation. The phase resolved partial discharge patterns acquired with a pattern recorder in such applications are bearing correlated distortions. Depending on the gas physics of the discharging site, for instance, some of the patterns are correlated to the AC voltage directly, while others are correlated to the voltage shape to the power of three (like with an ideal flat delamination). Further deviation of `real-life´ patterns vs. those obtained from controlled lab measurements is gained in case the measurement has to be taken far beyond the inception voltage
Keywords :
electric distortion; gas insulated switchgear; harmonics; partial discharge measurement; potential transformers; core saturation; distortion; electric field measurement; gas insulated switchgear; high voltage apparatus; phase resolved partial discharge pattern; power frequency harmonics; testing; voltage transformer; Distortion measurement; Frequency measurement; Gain measurement; Partial discharge measurement; Partial discharges; Phase distortion; Power measurement; Shape measurement; Voltage measurement; Voltage transformers;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
Conference_Location :
Atlanta, GA
Print_ISBN :
0-7803-5035-9
DOI :
10.1109/CEIDP.1998.732924