Mitigation of Power Supply Disturbance in Single-phase Loads
Author :
Basu, K.P.
Author_Institution :
Jadavpur Univ., Kolkata
fYear :
2006
fDate :
28-29 Nov. 2006
Firstpage :
254
Lastpage :
256
Abstract :
Voltage sag, short and long term power failures in single phase loads of a 3-phase system create voltage disturbance, which need to be mitigated immediately to improve the performance of the load. A 3-phase zigzag-winding transformer connected across a 3-phase star-connected load may mitigate the voltage disturbance at any one phase of the load. The phase experiencing the voltage disturbance is disconnected from the supply first. The zigzag transformer immediately rebuilds the voltage across the load of the open phase. Very low value of zero sequence impedance of the zigzag transformer provides a shunt path to the positive sequence current and, thereby, allows the current to flow to the open phase load.
Keywords :
power supply quality; power system faults; power transformers; power supply mitigation; voltage disturbance; voltage sag; zigzag-winding transformer; Batteries; Conductors; Electronic equipment; Energy storage; Impedance; Power quality; Power supplies; Power system transients; Switches; Voltage fluctuations; Voltage sag; open conductor; power interruption; zero sequence impedance; zigzag transformer;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Conference, 2006. PECon '06. IEEE International
Conference_Location :
Putra Jaya
Print_ISBN :
1-4244-0273-5
Electronic_ISBN :
1-4244-0274-3
Type :
conf
DOI :
10.1109/PECON.2006.346657
Filename :
4154501
Link To Document :
بازگشت