In this paper, the authors discuss the load characteristics of a steel factory containing a DC arc furnace. In order to reduce the cost, the arc furnace works during the off-peak period. While the furnace is in operation, the variation of active power and reactive power is quite large. In order to understand the load characteristics, the statistics method is used. The result shows that the large amount of reactive power variation is the main reason of voltage fluctuation. Although the DC arc furnace is operated in constant MVA mode, there is still obvious reactive power variation. A 12-pulse configuration and harmonic filters can reduce the harmonics generated by the DC furnace
Keywords :
AC-DC power convertors; arc furnaces; harmonic analysis; harmonic distortion; load (electric); power conversion harmonics; power harmonic filters; reactive power; rectifying circuits; steel industry; 12-pulse AC/DC power convertors; DC arc furnace; active power; constant MVA mode operation; harmonic analysis; harmonic filters; harmonics reduction; load characteristics; off-peak operation; reactive power variation; statistics method; steel factory; voltage fluctuation; Costs; Furnaces; Harmonic analysis; Harmonic filters; Power harmonic filters; Production facilities; Reactive power; Statistics; Steel; Voltage fluctuations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 2000. IEEE
Conference_Location :
Seattle, WA
Print_ISBN :
0-7803-6420-1
Type :
conf
DOI :
10.1109/PESS.2000.867452
Filename :
867452
Link To Document :
بازگشت