Title
Comparative dynamic analysis on frequency stabilization for multi-area power system in deregulated environment
Author
Bhateshvar, Y.K. ; Mathur, H.D.
Author_Institution
EEE Dept., BITS, Pilani, India
fYear
2012
fDate
15-17 March 2012
Firstpage
1
Lastpage
6
Abstract
This paper attempts to develop a linearized model of load frequency control (LFC) for an interconnected reheat type two-area thermal power system under deregulated environment. A conventional Integral controller is optimized using ISE optimization technique. A comparison between a conventional optimized integral controller and a fuzzy logic based controller is presented and the proposed fuzzy based controller is shown to generate the improved dynamic response following a step load change with combination of poolco and bilateral contracts in deregulated environment. In addition, performance of conventional integral controller and a fuzzy logic based controller is also examined under various changes up to ±30% in system parameters.
Keywords
frequency control; fuzzy control; load regulation; optimal control; power generation control; thermal power stations; ISE optimization technique; bilateral contracts; comparative dynamic analysis; deregulated environment; dynamic response; frequency stabilization; fuzzy logic based controller; integral controller; interconnected reheat type two-area thermal power system; linearized model; load frequency control; multiarea power system; optimized integral controller; poolco contracts; system parameters; Cost function; Frequency control; Fuzzy logic; Power system stability; Thermal loading; Two area power system; deregulated environment; fuzzy logic controller; integral controller; load frequency control;
fLanguage
English
Publisher
ieee
Conference_Titel
Signal Processing, Computing and Control (ISPCC), 2012 IEEE International Conference on
Conference_Location
Waknaghat Solan
Print_ISBN
978-1-4673-1317-9
Type
conf
DOI
10.1109/ISPCC.2012.6224351
Filename
6224351
Link To Document