DocumentCode :
2402827
Title :
Protection and Commissioning of Multifunction Digital Transformer Relays at Medium Voltage Industrial Facilities
Author :
Mozina, Charles J.
Author_Institution :
Beckwith Electr. Co. Inc., Largo, FL
fYear :
0
fDate :
0-0 0
Firstpage :
1
Lastpage :
11
Abstract :
The application of multifunction digital relays to protect medium voltage power transformers has become a common industrial practice. Industrial transformers, unlike utility transformers, frequently use neutral grounding resistors to limit ground current during faults to the 200-400 A level on medium voltage systems. This paper discusses why these types of transformers require sensitive ground differential protection. The paper also discusses the basics of transformer protection including: phasing standards, through-fault withstand capability, differential/fusing/ overcurrent protection, slope, CT requirements, harmonic restraint, and communicating these properly to new digital relays. The rationale for providing transformer overexcitation protection on all major transformers within mill facilities is also addressed. Advancements in digital technology have allowed relay manufacturers to include more and more relay functions within a single hardware platform as well as address increasingly more transformer winding configurations. This has resulted in digital transformer relays requiring an Einstein to set and an Edison to commission. Since there are few Einsteins or Edisons among us, the next generation of transformer relays needs to concentrate on this complexity issue in addition to technical improvements. This paper addresses these issues that the author believes are the major shortcomings of existing digital transformer protective relays
Keywords :
earthing; fault current limiters; harmonic analysis; overcurrent protection; power transformer protection; relay protection; current limit; harmonic restraint; medium voltage industrial facilities; multifunction digital power transformer relays; neutral grounding resistors; overcurrent protection; overexcitation protection; phasing standards; Digital relays; Electrical equipment industry; Grounding; Industrial plants; Medium voltage; Power system protection; Power system relaying; Power transformers; Protective relaying; Resistors; ANSI; E-M relays-; IEC; V/Hz; harmonic restraint; inrush; low-resistance grounding; multifunction digital relay; overexcitation; slope;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 2006 IEEE
Conference_Location :
Detroit, MI
Print_ISBN :
1-4244-0335-9
Type :
conf
DOI :
10.1109/ICPS.2006.1677279
Filename :
1677279
Link To Document :
بازگشت