DocumentCode :
2414140
Title :
Assessing the performance of a Static VAR Compensator for an electric arc furnace
Author :
Dionise, Thomas J.
Author_Institution :
Power Syst. Eng., Eaton Electr. Group, Warrendale, PA, USA
fYear :
2012
fDate :
7-11 Oct. 2012
Firstpage :
1
Lastpage :
10
Abstract :
The advantages of a Static VAR Compensator (SVC) for electric arc furnace (EAF) and ladle melt furnace (LMF) applications are well known. The SVC minimizes the impact of the EAF and LMF on the utility as well as improves the efficiency of both furnaces. In this application, it was desirable to quantify the performance of the SVC. This paper describes power quality measurements which were taken on the electrical distribution system to evaluate the performance of the SVC. The purpose of the power quality measurements was to monitor the voltage regulation, harmonics, flicker and other power quality quantities at the 138 kV utility point-of-common-coupling (PCC) as well as the 34.5 kV system serving the SVC, EAF and LMF. The measurements and subsequent analysis established a baseline for the SVC performance and identified areas of concern. This paper describes the analysis of the measurements and evaluation of the SVC performance.
Keywords :
arc furnaces; power supply quality; static VAr compensators; EAF; LMF; SVC; electric arc furnace; electrical distribution system; point-of-common-coupling; power quality measurements; power quality quantities; static VAR compensator; voltage 138 kV; voltage 34.5 kV; Arc discharges; Decision support systems; Static VAr compensators; IEEE Std 1453–2004; IEEE Std 519–1992; electric arc furnace; flicker; harmonic distortion; static var compensator;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting (IAS), 2012 IEEE
Conference_Location :
Las Vegas, NV
ISSN :
0197-2618
Print_ISBN :
978-1-4673-0330-9
Electronic_ISBN :
0197-2618
Type :
conf
DOI :
10.1109/IAS.2012.6374067
Filename :
6374067
Link To Document :
بازگشت