DocumentCode
2414441
Title
Experience with on-line partial discharge analysis as a tool for predictive maintenance for medium voltage (MV) switchgear systems
Author
Smith, James E. ; Paoletti, Gabe ; Blokhintsev, Lgor
Author_Institution
Cutler-Hammer, Pittsburgh, PA, USA
fYear
2002
fDate
2002
Firstpage
155
Lastpage
161
Abstract
Partial discharge (PD) online monitoring of MV switchgear was implemented in several large industrial plants beginning in 1998. A switchgear manufacturer completed offline testing and calibration to determine the type and location of sensors for measuring the effective sensitivity of partial discharge activity. This paper also presents actual pending failures, which were identified and prevented by online PD monitoring. The pending failures include bus corona damage, CT corona damage and failing insulation due to surface tracking. An update of new continuous online partial discharge monitors for MV switchgear is also included.
Keywords
corona; insulation testing; maintenance engineering; monitoring; partial discharge measurement; switchgear; switchgear testing; MV switchgear; bus corona damage; corona damage; fairing insulation; industrial plants; partial discharge activity; partial discharge online monitoring; pending failures; surface tracking; Calibration; Condition monitoring; Corona; Industrial plants; Manufacturing; Medium voltage; Partial discharges; Predictive maintenance; Switchgear; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Petroleum and Chemical Industry Conference, 2002. Industry Applications Society 49th Annual
ISSN
0090-3507
Print_ISBN
0-7803-7384-7
Type
conf
DOI
10.1109/PCICON.2002.1044997
Filename
1044997
Link To Document