DocumentCode :
2414919
Title :
Transient recovery voltages caused by capacitor switching in wind power plants
Author :
Badrzadeh, Babak
Author_Institution :
Syst. Capability, Australian Energy Market Operator, Melbourne, VIC, Australia
fYear :
2012
fDate :
7-11 Oct. 2012
Firstpage :
1
Lastpage :
8
Abstract :
This paper investigates transient recovery voltages across vacuum circuit breakers used for switching mechanically switched shunt capacitor banks in a wind power plant. Simulation case studies are conducted which investigate the transient recovery voltages with the original bank configuration, and a number of modified configurations. It is shown that using the original configuration, with inrush current limiting reactor in series with the capacitor, can result in a breaker failure under most onerous conditions. A number of alternative configurations are proposed which allow management of transient recovery voltages within the breaker withstand level.
Keywords :
capacitor switching; transients; vacuum circuit breakers; wind power plants; capacitor switching; switching mechanical switched shunt capacitor banks; transient recovery voltage; vacuum circuit breakers; wind power plants; Capacitors; Circuit breakers; Dielectric breakdown; Inductors; Surge protection; Transient analysis; Wind turbine generator; circuit breaker restrike and reignition; high frequency transients; mechanically switched capacitor; transient recovery voltages;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting (IAS), 2012 IEEE
Conference_Location :
Las Vegas, NV
ISSN :
0197-2618
Print_ISBN :
978-1-4673-0330-9
Electronic_ISBN :
0197-2618
Type :
conf
DOI :
10.1109/IAS.2012.6374100
Filename :
6374100
Link To Document :
بازگشت