Abstract :
The feature of partial discharge (PD) is an important aspect of generators´ insulation. The paper introduces an automatic online PD monitoring system for large turbine generators. By using digital signal processor (DSP) sampling technology, the system can obtain a long duration PD signal with high sampling rate. Fast Fourier transform (FFT) analysis, finite impulse response (FIR) filter, Adaptive filter and Wavelet analysis have been used in data processing. DSP, high performance industry computer and multi-CPU server provide powerful ability for data processing. client/server structure and fiber distributed data interface (FDDI) network have been used in the system, so it can be expand to the distributing monitoring system for monitoring several generators in the same power plant simultaneously. Information of PD pulse can be kept in the database in server permanently; it can be used to follow the track of large generators aging. The system can recognize several typical PD in large turbine generator. Results from large turbine generators are given at the end of the paper
Keywords :
Fourier analysis; computerised monitoring; fast Fourier transforms; insulation testing; machine insulation; machine testing; partial discharge measurement; power engineering computing; telemetry; turbogenerators; PD online monitoring system development; adaptive filter; client/server structure; digital signal processor; fast Fourier transform analysis; fiber distributed data interface network; finite impulse response filter; large turbine-generators; sampling rate; sampling technology; wavelet analysis; Adaptive filters; Computerized monitoring; Data processing; Digital signal processing; FDDI; Finite impulse response filter; Network servers; Partial discharges; Signal sampling; Turbines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on
Conference_Location :
Boston, MA
Print_ISBN :
0-7803-7337-5
Type :
conf
DOI :
10.1109/ELINSL.2002.995872
Filename :
995872
Link To Document :
بازگشت