DocumentCode :
2418928
Title :
Interpretation of RVM measurements, beyond the polarisation spectrum
Author :
van Bolhuis, J.P. ; Gulski, E. ; Smit, J.J. ; Pepper, D.
Author_Institution :
High Voltage Technol. & Manage., Delft Univ. of Technol., Netherlands
fYear :
2002
fDate :
7-10 Apr 2002
Firstpage :
179
Lastpage :
182
Abstract :
Much has been said about the reliability and interpretation of recovery voltage method (RVM) measurements. It has been shown in literature that the RVM method can be used to detect local moisture ingress in transformers, but also it has been shown that the old interpretation of the ´dominant time constant´ has been found wanting. An important failure of the ´dominant time constant´ interpretation is that it both focusses the user on a too simple interpretation and neglects data on other quantities that have also been recorded during this measurement. This paper deals with the all quantities that are recorded during an RVM measurement and shows how to use them so that they can form the basis of a better way to interpret RVM measurements.
Keywords :
dielectric polarisation; insulation testing; power transformer insulation; power transformer testing; voltage measurement; RVM measurements; dielectric response methods; dominant time constant interpretation; local moisture ingress detection; power transformer insulation diagnostics; recovery voltage method; Instruments; Moisture; Polarization; Power transformers; Strontium; Surface resistance; Technology management; Testing; Time measurement; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on
Print_ISBN :
0-7803-7337-5
Type :
conf
DOI :
10.1109/ELINSL.2002.995907
Filename :
995907
Link To Document :
بازگشت