DocumentCode :
2420711
Title :
Restoration of ground-wall armor of stator bars exposed to slot discharges
Author :
Hudon, C. ; Belec, M. ; Guddemi, C. ; Nguyen, Su ; Nguyen, Duc N.
Author_Institution :
Inst. de Recherche, Hydro-Quebec, Varennes, Que.
fYear :
2002
fDate :
7-10 Apr 2002
Firstpage :
497
Lastpage :
501
Abstract :
Slot discharges have been reproduced under well controlled laboratory conditions. Semi-conductive paint was then injected through the ventilation ducts along the side of the bars, without removing the bars or the radial wedges. Partial discharge measurements showed that the slot discharge had completely disappeared from 5 out of the 6 bars, and considerably reduced on the last bar. This last bar was one with tight lateral clearance, thus the paint could not easily infiltrate and restore the damaged area. Partial discharge results, surface observations and a conclusion with respect to the precautions and effectiveness of this correction are presented.
Keywords :
insulation testing; machine insulation; partial discharge measurement; stators; ventilation; ground-wall armor restoration; partial discharge measurements; radial wedges; semi-conductive paint; slot discharges; stator bars; surface observations; tight lateral clearance; ventilation ducts; Ducts; Insulation; Laboratories; Paints; Partial discharge measurement; Partial discharges; Production; Stator bars; Stator windings; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on
Print_ISBN :
0-7803-7337-5
Type :
conf
DOI :
10.1109/ELINSL.2002.995983
Filename :
995983