DocumentCode :
2427911
Title :
Update on UPS battery life characteristics
Author :
Misra, Sudhan S. ; Holden, Leslie S. ; Williamson, Allan J.
Author_Institution :
C&D Technologies Inc., Conshohocken, PA, USA
fYear :
1998
fDate :
13-16 Jan 1998
Firstpage :
279
Lastpage :
284
Abstract :
A 1991 paper from C&D had reviewed the problem of large scale premature failure facing many UPS batteries at the time. It analyzed the failure modes and the causes for the premature failure of early designs. It also discussed the improvements to the design, already in place, to overcome the problems. Improved performance was predicted on the basis of accelerated tests that had progressed only partially forward. Completed data from the accelerated tests and more than ten years´ field experience with these improved designs are reported here, vindicating the change. Also discussed are five years´ field experience with a utility battery for frequency regulation-the PREPA battery, which is a massive and heavily cycled UPS battery. Valve regulated batteries, which had relatively less exposure at the time of the earlier paper, have since had a build up of experience; the authors´ experience is discussed
Keywords :
life testing; secondary cells; uninterruptible power supplies; PREPA battery; UPS battery life characteristics; accelerated tests; frequency regulation; performance improvements; premature failure; utility battery; valve regulated batteries; Batteries; Failure analysis; Frequency; Large-scale systems; Life estimation; Manufacturing; Paper technology; Testing; Uninterruptible power systems; Valves;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Battery Conference on Applications and Advances, 1998., The Thirteenth Annual
Conference_Location :
Long Beach, CA
ISSN :
1089-8182
Print_ISBN :
0-7803-4098-1
Type :
conf
DOI :
10.1109/BCAA.1998.653880
Filename :
653880