DocumentCode
2430388
Title
Power factor correction of a single-phase on-line UPS with the half-bridge inverter
Author
Chen, Yie-Tone
Author_Institution
Dept. of Electr. Eng., Nat. Yunlin Inst. of Technol., Taiwan
Volume
3
fYear
1996
fDate
5-10 Aug 1996
Firstpage
1826
Abstract
The power factor correction (PFC) scheme of the conventional on-line UPS with the half-bridge inverter is proposed and described. A correction method for the positive voltage boost stage is like the well-established boost corrector, but the PFC circuit of the negative voltage boost stage is different. The power factor of unbalanced loads can be still close to unity by the proposed scheme. Design considerations for the half-power positive or negative boost corrector are also presented and discussed. The experiment has been conducted to verify the proposed circuit
Keywords
bridge circuits; invertors; power factor correction; uninterruptible power supplies; half-bridge inverter; half-power negative boost corrector; half-power positive boost corrector; negative voltage boost stage; positive voltage boost stage; power factor correction; single-phase on-line UPS; unbalanced loads; Circuits; Inverters; Power factor correction; Power quality; Power supplies; Reactive power; Switches; Telecommunication computing; Uninterruptible power systems; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics, Control, and Instrumentation, 1996., Proceedings of the 1996 IEEE IECON 22nd International Conference on
Conference_Location
Taipei
Print_ISBN
0-7803-2775-6
Type
conf
DOI
10.1109/IECON.1996.570746
Filename
570746
Link To Document