  • Abstract
    Most faults in ungrounded neutral systems are single-phase earthing. Because of the influence of arcing and operating manners, the accuracy of fault line selection algorithms using steady zero sequence current is not satisfactory. In this paper, the effects of arcing on the accuracy of fault line selection are detailed after studying the zero-sequence current during arcing faults. The Clarke transform is employed and the wavelets transform is also adopted to develop a novel method for fault line selection. EMTP is employed to simulating the arcing faults and the simulation is performed under various sampling frequencies and A/D resolution. The results show that the novel method is valid, effective and robust.
  • Keywords
    EMTP; earthing; fault location; power system analysis computing; power system faults; power system protection; wavelet transforms; Clarke transform; EMTP; arcing faults; computer simulation; fault line selection algorithm; single-phase earthing; single-phase ground faults; ungrounded neutral system; wavelets transform; Circuit faults; Coils; EMTP; Fault currents; Frequency; Grounding; Impedance; Sampling methods; Transient analysis; Wavelet transforms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
  • Print_ISBN
    0-7803-7459-2
  • Type

    conf

  • DOI
    10.1109/ICPST.2002.1047242
  • Filename
    1047242