DocumentCode
2445301
Title
A new selective transient protection for the ground fault of large unit-connected generators
Author
Daqiang, Bi ; Weijian, Wang ; Lin, Gui ; Xiangheng, Wang
Author_Institution
Dept. of Electr. Eng. & Appl. Electron. Technol., Tsinghua Univ., Beijing, China
Volume
4
fYear
2002
fDate
2002
Firstpage
2622
Abstract
Based on the multi-loop circuit method of AC machine a mathematic model is established for the large unit-connected generators, namely the outlet terminal of generators connected to a common busbar, and the transient zero-sequence current and voltage of these generators are simulated and analyzed at different grounding location. Further, making use of the wavelet transform sensitively detecting the singularity of signal, the properties of their value of wavelet transform are analyzed, and a selective transient protection is proposed according to the sign and value of the modulus maxima of wavelet transform. The results of simulation and experiment verify the new protection can correctly detect the generator with ground fault, and discriminate between the internal and external faults.
Keywords
AC generators; earthing; electrical faults; machine protection; wavelet transforms; AC machine; common busbar; external faults; ground fault; grounding location; internal faults; mathematic model; modulus maxima; multi-loop circuit method; outlet terminal; selective transient protection; signal singularity detection; transient zero-sequence current; transient zero-sequence voltage; unit-connected generators; wavelet transform; wavelet transform sensitively; AC generators; AC machines; Circuit faults; Mathematical model; Mathematics; Protection; Transient analysis; Voltage; Wavelet analysis; Wavelet transforms;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN
0-7803-7459-2
Type
conf
DOI
10.1109/ICPST.2002.1047261
Filename
1047261