Title :
A novel algorithm for differential protection of untransposed transmission line using synchronized measurements
Author :
Dahane, A.S. ; Dambhare, S.S.
Author_Institution :
Department of Electrical Engineering, College of Engineering, Pune-411005, India
Abstract :
Although there has been a practice of transposition of transmission lines, most of the real life EHV/UHV lines are untransposed. The distance protection of such lines becomes very complicated. With the advent of Global Positioning System (GPS) and Fiber optics technology, current differential protection can be a better choice for such lines. This paper proposes current differential protection scheme for protection of untransposed transmission lines based on equivalent-π line model. The proposed differential relay basically works on difference of currents in series branch (computed) from equivalent-π line model. As the measurements are time synchronized, the performance of relay is immune to line charging current. The analysis has been carried out in phase coordinates. ATP/EMTP programs have been used to simulate system disturbance and algorithm is implemented MATLAB. The result shows the efficacy and robustness of proposed algorithm.
Keywords :
Circuit faults; Mathematical model; Power transmission lines; Relays; Synchronization; Transmission line matrix methods; Transmission line measurements; ATP/EMTP; Current differential protection; equivalent-π model; synchronised phasor measurements; untransposed line;
Conference_Titel :
Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
Conference_Location :
Birmingham, UK
Print_ISBN :
978-1-84919-620-8
DOI :
10.1049/cp.2012.0025