DocumentCode
2446080
Title
Enhancing differential protection stability during CT saturation with Transient Bias
Author
Bagleybter, O. ; Subramanian, Sivaraman
Author_Institution
Alstom Grid UK Ltd, UK
fYear
2012
fDate
23-26 April 2012
Firstpage
1
Lastpage
4
Abstract
The paper describes a Transient Bias technique designed to overcome the effects of Current Transformer (CT) saturation, which might severely affect the behaviour of a protection system. This Transient Biasing, as the name implies, is only active during transient conditions in the power system, and it decays quickly once the transients disappear. A complementary algorithm for fast detection of external faults is proposed, which prevents the Transient Bias feature from increasing the differential protection operating time in case of internal faults. The operation of current differential protection with Transient Bias is checked using Simulink® models of the relay and current transformer. In addition, the paper reviews the results of RTDS® tests carried out with actual current differential relays and provides detailed information on CT requirements testing method adopted by Alstom Grid.
Keywords
Current transformers; Fault currents; Relays; Remanence; Testing; Transient analysis; CT modelling; CT requirements; Current differential protection; transient biasing;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
Conference_Location
Birmingham, UK
Print_ISBN
978-1-84919-620-8
Type
conf
DOI
10.1049/cp.2012.0036
Filename
6227522
Link To Document