  • Abstract
    High impedance fault (HIF) exposes great hazard for personal safety and property security. High impedance fault (HIF) in MV distribution with restricted fault current cannot be detected and cleared by conventional over current relays. In this paper, an integrated scheme utilizing different features of HIF is presented. Various documented field data has been investigated and summarized to get the most distinctive features of HIF. Based on these features, a simulation model using arc thermal equation and random factor has been developed. The integrated scheme investigates into different scopes of the fault features ranging from transient high frequency, harmonic distortion to fundamental intermittent. EMTP (Electromagnetic Transients Program) simulation results show that the integrated scheme can detect most HIFs and discriminate HIF from other interference scenarios such as CT saturation, load nonlinearity and capacity transients. Therefore, this scheme achieves a better result with reliability and security.
  • Keywords
    Arrays; Equations; Fault currents; Feature extraction; Harmonic analysis; Mathematical model; Resistance; EMTP; Harmonic; High Impedance Fault; Intermittent; Wavelet;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
  • Conference_Location
    Birmingham, UK
  • Print_ISBN
    978-1-84919-620-8
  • Type

    conf

  • DOI
    10.1049/cp.2012.0080
  • Filename
    6227568