DocumentCode
2447755
Title
Impedance based fault location method for phase to phase and three phase faults in transmission systems
Author
Shateri, H. ; Jamali, Shahram
Author_Institution
Centre of Excellence for Power Systems Automation and Operation, Iran University of Science and Technology, Tehran - Iran
fYear
2012
fDate
23-26 April 2012
Firstpage
1
Lastpage
5
Abstract
This paper presents a new impedance based fault location method in the case of phase to phase and three phase faults. This method utilized the measured impedance by distance relay and super imposed current factor, which is the ratio of post-fault current to super imposed current, to discriminate the fault position on the line. This method is robust against the fault resistance. The presented method only uses the measured impedance by distance relay, the super imposed current factor and few data which could be achieved through the SCADA based databases.
Keywords
Circuit faults; Electrical resistance measurement; Fault location; Impedance; Impedance measurement; Resistance; Transmission line measurements; Fault location; Impedance based method; Measured impedance; Transmission line;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
Conference_Location
Birmingham, UK
Print_ISBN
978-1-84919-620-8
Type
conf
DOI
10.1049/cp.2012.0108
Filename
6227596
Link To Document