DocumentCode
2449613
Title
Improvement of subharmonic injection schemes for huge hydro-generator stator ground fault protection
Author
Xiangjun, Zeng ; Xianggen, Yin ; Gan, Lin ; Sheng, Su ; Deshu, Chen
Author_Institution
Dept. of Electr. Eng., Changsha Univ. of Electr. Power, China
Volume
2
fYear
2002
fDate
2002
Firstpage
707
Abstract
The stator winding of huge hydrogenerator unit has large leakage capacitance to earth. Traditional subharmonic injection schemes for generator stator grounding fault protection have poor performance in detecting high impedance grounding faults (HIGF). In order to improve them, a reactor added in parallel with the resistance in the secondary of a neutral grounding distribution transformer is applied to compensate the leakage capacitance in the paper. By measuring the voltage and current of the resonant signal injected from the additional reactor, grounding fault resistance can be calculated directly and HIGF protection for 100% generator stator windings is proposed. Simulation results show that the improved subharmonic injection scheme can detect HIGF with fault resistance higher than 8 kΩ.
Keywords
compensation; earthing; harmonic distortion; hydroelectric generators; machine protection; machine theory; power generation faults; power system harmonics; stators; 8 kohm; current measurement; grounding fault resistance; high impedance grounding faults; large hydrogenerator stator ground fault protection; leakage capacitance compensation; neutral grounding distribution transformer; subharmonic injection schemes improvement; voltage measurement; Capacitance; Current measurement; Earth; Electrical resistance measurement; Fault detection; Grounding; Impedance; Inductors; Protection; Stator windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN
0-7803-7459-2
Type
conf
DOI
10.1109/ICPST.2002.1047489
Filename
1047489