Title :
Research on non-communication protection of distribution lines based on fault components
Author :
Jianguang, Bi ; Xinzhou, Dong ; Yongji, Guo ; Zhiqian, Bo
Author_Institution :
Tsinghua Univ., Beijing, China
Abstract :
When distribution power lines run normally, there is asymmetrical current and voltage component including negative sequence and zero sequence components. So non-communication protection based on sequence components might mal-operate or mis-operate in the cases. The paper proposed a new noncommunication protection scheme based on fault component for distribution line. The protection can be applied to different neutral grounding mode including direct and indirect grounding neutral system and isn´t affected by normal running asymmetrical component. According to the fault component (or the incremental quantities of three sequence component), it can assure that one end breaker of fault line trips as quickly as possible and other end breaker is accelerated to trip. Simulation shows that the protection scheme is both correct and effective.
Keywords :
circuit breakers; earthing; power distribution faults; power distribution lines; power distribution protection; asymmetrical current component; asymmetrical voltage component; distribution lines noncommunication protection; end breaker; fault components; fault line trips; negative sequence components; neutral grounding mode; three sequence component; zero sequence components; Acceleration; Bismuth; Circuit faults; Grounding; Investments; Power system analysis computing; Power system modeling; Power system protection; Power system simulation; Voltage;
Conference_Titel :
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN :
0-7803-7459-2
DOI :
10.1109/ICPST.2002.1047582