DocumentCode
2455603
Title
Control strategy for a series active filter for the neutral conductor in a building and its installation point
Author
Wada, Keiji ; Inoue, Shigenori ; Shimizu, Toshihisa
Author_Institution
Dept. of Electr. Eng., Tokyo Inst. of Technol., Japan
Volume
2
fYear
2003
fDate
12-16 Oct. 2003
Firstpage
1203
Abstract
This paper presents control strategy of the series active filter connected to the neutral conductor on the three-phase four-wire distribution system in a building. Harmonic distortion in the building is measured, and it is clarified that the third-harmonic voltage on the upper floor is larger than that on the lower floor because of the influence of line inductances between each floor. The optimum installation point of the active filter in the multi-story buildings is presented. In addition, control strategy for the DC bus voltage in the active filter is studied. Experimental results obtained from a 200-V, 3-kVA laboratory system verify the effectiveness of the series active filter.
Keywords
active filters; distribution networks; harmonic distortion; inductance; power harmonic filters; power system harmonics; voltage control; 200 V; 3 kVA; DC bus voltage; control strategy; harmonic distortion measurement; installation point; line inductances; multi-story buildings; neutral conductor; optimum installation point; series active filter; third-harmonic voltage; three-phase four-wire distribution system; Active filters; Conductors; Control systems; Electronic mail; Floors; Harmonic distortion; Power distribution; Power harmonic filters; Power system harmonics; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 2003. 38th IAS Annual Meeting. Conference Record of the
Print_ISBN
0-7803-7883-0
Type
conf
DOI
10.1109/IAS.2003.1257703
Filename
1257703
Link To Document