• DocumentCode
    2455603
  • Title

    Control strategy for a series active filter for the neutral conductor in a building and its installation point

  • Author

    Wada, Keiji ; Inoue, Shigenori ; Shimizu, Toshihisa

  • Author_Institution
    Dept. of Electr. Eng., Tokyo Inst. of Technol., Japan
  • Volume
    2
  • fYear
    2003
  • fDate
    12-16 Oct. 2003
  • Firstpage
    1203
  • Abstract
    This paper presents control strategy of the series active filter connected to the neutral conductor on the three-phase four-wire distribution system in a building. Harmonic distortion in the building is measured, and it is clarified that the third-harmonic voltage on the upper floor is larger than that on the lower floor because of the influence of line inductances between each floor. The optimum installation point of the active filter in the multi-story buildings is presented. In addition, control strategy for the DC bus voltage in the active filter is studied. Experimental results obtained from a 200-V, 3-kVA laboratory system verify the effectiveness of the series active filter.
  • Keywords
    active filters; distribution networks; harmonic distortion; inductance; power harmonic filters; power system harmonics; voltage control; 200 V; 3 kVA; DC bus voltage; control strategy; harmonic distortion measurement; installation point; line inductances; multi-story buildings; neutral conductor; optimum installation point; series active filter; third-harmonic voltage; three-phase four-wire distribution system; Active filters; Conductors; Control systems; Electronic mail; Floors; Harmonic distortion; Power distribution; Power harmonic filters; Power system harmonics; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2003. 38th IAS Annual Meeting. Conference Record of the
  • Print_ISBN
    0-7803-7883-0
  • Type

    conf

  • DOI
    10.1109/IAS.2003.1257703
  • Filename