DocumentCode
2460792
Title
The effect of the stray cable parameters on the HF interrupting capacity of VCB
Author
Chaly, Alexy M. ; Chalaya, Alevtina T. ; Poluyanov, Victor N. ; Poluyanova, Irina N.
Author_Institution
Tavrida Electr. Ltd., Sevastopol, Russia
Volume
2
fYear
1998
fDate
17-21 Aug 1998
Firstpage
431
Abstract
HF interruption behaviour of vacuum circuit breakers (VCB) is very important for analysis of switching surges induced at interruption of inductive load by VCB. In an actual network, HF current is produced when a power cable is discharged through VCB separating contacts. Many researchers dealt with this problem by simulating an actual cable by LC circuit with lumped elements. We have conducted experimental research concerning HF interruption behaviour of VCB with CuCr contacts at interruption of the “artificial” cable and equivalent single-frequency LC circuit. The experimental results revealed a strong effect of cable stray parameters on the VCB HF interruption behaviour
Keywords
electrical contacts; equivalent circuits; power cables; surges; switching; vacuum circuit breakers; CuCr contacts; HF interrupting capacity; cable simulation; equivalent single-frequency LC circuit; inductive load interruption; separating contacts; stray cable parameters; switching surges analysis; vacuum circuit breakers; Capacitors; Circuit simulation; Frequency; Hafnium; Interrupters; Power cables; Resistors; Surges; Switches; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 1998. Proceedings ISDEIV. XVIIIth International Symposium on
Conference_Location
Eindhoven
ISSN
1093-2941
Print_ISBN
0-7803-3953-3
Type
conf
DOI
10.1109/DEIV.1998.738626
Filename
738626
Link To Document