DocumentCode :
2460948
Title :
Unbalanced three-phase control using offset-voltage for H-bridge multilevel inverter with faulty power cells
Author :
Park, Young-Min ; Lyoo, Han-Seoung ; Lee, Hyun-Won ; Jung, Myung-Gil ; Lee, Se-Hyun ; Yoo, Ji-Yoon
Author_Institution :
Hyundai Heavy Ind. Co. Ltd., Seoul
fYear :
2008
fDate :
15-19 June 2008
Firstpage :
1790
Lastpage :
1795
Abstract :
In this paper, unbalanced three-phase control method is proposed to increase the fault tolerance for H-bridge multilevel inverter under the conditions of faulty power cells. It is possible to generate a balanced three-phase line-to-line voltage by phase-shifting and bypassing faulty power cells with a minimum voltage drop. In this method, the concept of voltage modulation by using offset voltage is applied to an unbalanced three-phase control method. Especially, it is possible to use the maximum output voltage of inverter by adopting the real time unbalanced control method of phase voltage irrespective of the fault location and the number of disabled power cells. Also, the feasibility of the proposed method is proved by the H-bridge multilevel inverter test composed of 7-level.
Keywords :
bridge circuits; invertors; voltage control; H-bridge multilevel inverter; fault tolerance; faulty power cells; inverter output voltage; offset-voltage; three-phase line-to-line voltage; unbalanced three-phase control; voltage drop; voltage modulation; Fault location; Fault tolerance; Industrial control; Power generation; Power system reliability; Power transformers; Pulse width modulation inverters; Switches; Testing; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2008. PESC 2008. IEEE
Conference_Location :
Rhodes
ISSN :
0275-9306
Print_ISBN :
978-1-4244-1667-7
Electronic_ISBN :
0275-9306
Type :
conf
DOI :
10.1109/PESC.2008.4592203
Filename :
4592203
Link To Document :