DocumentCode :
2460977
Title :
Methods for internal pressure diagnostic of vacuum circuit breakers
Author :
Frontzek, F.R. ; König, D.
Author_Institution :
Dept. of Electr. Power Eng., Polytech. Univ. Darmstadt, Germany
Volume :
2
fYear :
1998
fDate :
17-21 Aug 1998
Firstpage :
467
Abstract :
Vacuum circuit breakers are compact and require little maintenance. However, after several years of service, an inspection of vacuum interrupters is recommended to verify that the vacuum level in the vacuum chambers is still adequate. Rise of internal pressure exceeding a certain threshold value causes loss of current switching capability and electric insulating properties. It is common practice to perform pressure measurements in the factory on new vacuum chambers with a measuring system usually based on the well known magnetron principle. However, pressure measurements on new vacuum chambers after manufacturing and verification of vacuum in circuit breakers after several years of service require different test procedures and diagnostic techniques. Users of vacuum circuit breakers are interested in a simple method suitable for application on the site which aim at checking whether a given pressure threshold value is not yet exceeded. In this paper an overview of ideas, patents and procedures for internal pressure diagnostics of vacuum circuit breakers is presented and the feasibility for application on the site for the circuit breaker vacuum monitoring system is discussed
Keywords :
inspection; maintenance engineering; switching; vacuum circuit breakers; vacuum insulation; vacuum interrupters; vacuum measurement; EM wave signals; X-rays; arc voltage; breakdown voltage; current switching capability loss; diagnostic techniques; electric insulating properties; emission currents; heat transfer; inspection; internal pressure diagnostic; internal pressure rise; magnetron; maintenance; prebreakdown curents; pressure measurements; test procedures; threshold value; vacuum chambers; vacuum circuit breakers; vacuum interrupters; vacuum level; vacuum monitoring system; Circuit breakers; Circuit testing; Dielectrics and electrical insulation; Inspection; Interrupters; Performance evaluation; Pressure measurement; Production facilities; Vacuum systems; Vacuum technology;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1998. Proceedings ISDEIV. XVIIIth International Symposium on
Conference_Location :
Eindhoven
ISSN :
1093-2941
Print_ISBN :
0-7803-3953-3
Type :
conf
DOI :
10.1109/DEIV.1998.738634
Filename :
738634
Link To Document :
بازگشت