DocumentCode :
2461108
Title :
Measurement and research on the best electrode separation for 35 kV vacuum interrupters
Author :
Li, Jin ; Feng, Zhou ; Jing, Yan ; Jimei, Wang
Author_Institution :
Xi´´an Jiaotong Univ., China
Volume :
2
fYear :
1998
fDate :
17-21 Aug 1998
Firstpage :
484
Abstract :
A synthetic circuit is used to measure and research 35 kV exposed shield-type vacuum interrupters with cup axial magnetic field-type electrodes. Experimental results show that there is a limitation of the best separation for 35 kV vacuum interrupters. In this range, the probability of reignition is lower and the post arc withstand-voltage is higher. This paper analyzes the experimental results and points out that it is necessary to reduce the contact spacing of vacuum interrupters and vacuum circuit breakers
Keywords :
circuit-breaking arcs; electrodes; magnetic fields; switchgear testing; vacuum circuit breakers; vacuum interrupters; 35 kV; best separation; contact spacing reduction; cup axial magnetic field-type electrodes; electrode separation; exposed shield-type vacuum interrupters; post arc withstand-voltage; reignition probability; switchgear tests; vacuum circuit breakers; Circuit breakers; Circuit testing; Dielectrics and electrical insulation; Electrodes; Interrupters; Magnetic field measurement; System testing; Vacuum arcs; Vacuum technology; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1998. Proceedings ISDEIV. XVIIIth International Symposium on
Conference_Location :
Eindhoven
ISSN :
1093-2941
Print_ISBN :
0-7803-3953-3
Type :
conf
DOI :
10.1109/DEIV.1998.738642