Abstract :
3-phase AC-drives for HVAC applications (heating, ventilation & air-conditioning) typically employ a passive diode rectifier and an electrolytic DC-link capacitor to filter the rectified line voltage. The DC capacitor may be accompanied by AC or DC-chokes for harmonic line- current reduction. Recently, commercial HVAC drives, where all traditional passive rectifier components are replaced with a "small" DC-link film capacitor, have emerged. These are referred to as slim DC-link AC-drives. This AC-drive is compared to traditional types below.
Keywords :
HVAC; diodes; electric drives; rectifiers; 3-phase AC-drives; AC-chokes; DC capacitor; DC-chokes; DC-link topology; HVAC; air-conditioning; electrolytic DC-link capacitor; harmonic line-current reduction; heating; passive diode rectifier; passive front-ends; ventilation; Attenuation; Capacitors; Circuit topology; Diodes; Heating; Inductors; Rectifiers; Switched-mode power supply; Ventilation; Voltage;