DocumentCode
2469883
Title
Three phase power factor corrected isolated buck for 48 V/100 A rectifier with secondary active clamp
Author
Sheehy, Robert ; Dekter, Jurien ; Machin, Nigel
Author_Institution
Rectifier Technol., Melbourne, Vic., Australia
fYear
2002
fDate
2002
Firstpage
101
Lastpage
106
Abstract
A novel active clamp circuit for the secondary diodes of an isolated three phase buck converter is presented. The voltage spike on the diodes is clamped to permit the use of lower voltage rating diodes and the energy trapped in the transformer leakage inductance due to the reverse recovery current of the diodes is recycled to the output. The principle of operation of the active clamp with the three phase buck is analyzed and verified on a 6 kW prototype.
Keywords
inductance; magnetic leakage; power factor correction; power semiconductor diodes; rectifying circuits; transformers; 100 A; 48 V; 6 kW; active lossless clamp circuit principles; energy trapping; isolated three phase buck converter; lower voltage rating diodes; rectifier; reverse recovery current; secondary active clamp; secondary diodes; three phase power factor corrected isolated buck converter; transformer leakage inductance; voltage spike clamping; Buck converters; Circuits; Clamps; Diodes; Frequency conversion; Reactive power; Rectifiers; Stress; Switches; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN
0-7803-7512-2
Type
conf
DOI
10.1109/INTLEC.2002.1048641
Filename
1048641
Link To Document