DocumentCode :
2469904
Title :
Modern circuit topology enables compact power factor corrected three-phase rectifier module
Author :
Backman, N. ; Rojas, Roberto
Author_Institution :
Emerson Energy Syst., Stockholm, Sweden
fYear :
2002
fDate :
2002
Firstpage :
107
Lastpage :
114
Abstract :
A three phase, power factor corrected, 48 V/11 kW rectifier for telecom applications is described. The choice of electrical circuit topologies, three-level three-phase boost converter for the PFC, and the matching three-level DC/DC-converter for isolation and output voltage regulation, enable a very compact, 600 W/liter, and efficient, >93%, rectifier module.
Keywords :
DC-DC power convertors; power factor correction; rectifying circuits; telecommunication power supplies; voltage control; 11 kW; 48 V; circuit topology; electrical circuit topologies; output voltage regulation; power factor corrected three-phase rectifier module; telecom applications; three-level DC/DC-converter; three-level three-phase boost converter; Circuit topology; Frequency; MOSFETs; Power conversion; Power factor correction; Pulse width modulation; Reactive power; Rectifiers; Telecommunications; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN :
0-7803-7512-2
Type :
conf
DOI :
10.1109/INTLEC.2002.1048642
Filename :
1048642
Link To Document :
بازگشت