DocumentCode
2469959
Title
Study of scattering of VRLA batteries characteristics and its influence for UPS applications
Author
Rossinot, E. ; Lefrou, C. ; Cun, J.P.
Author_Institution
MGE UPS Syst., Saint Ismier, France
fYear
2002
fDate
2002
Firstpage
128
Lastpage
133
Abstract
Scattering of various electrical characteristics of VRLA batteries was measured under controlled conditions, using batteries from three different manufacturers. Data on open-circuit voltage, capacity and float parameters (currents, voltages and impedances) were collected for new, fully charged batteries. The relevance of each parameter is discussed in regard to the industrial question of the often observed accelerated aging of VRLA batteries placed in series in UPS applications.
Keywords
ageing; electric current measurement; electric impedance measurement; lead acid batteries; uninterruptible power supplies; voltage measurement; 12 V; Pb; Pb-acid valve regulated batteries; UPS applications; VRLA batteries; accelerated aging; capacity; controlled conditions; current measurement; electrical characteristics measurement; float parameters; fully charged batteries; impedance measurement; open circuit voltage; voltage measurements; Accelerated aging; Battery charge measurement; Corrosion; Electric variables; Electric variables measurement; Electrodes; Manufacturing; Scattering parameters; Uninterruptible power systems; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN
0-7803-7512-2
Type
conf
DOI
10.1109/INTLEC.2002.1048645
Filename
1048645
Link To Document