Title :
Guidelines for power-supply systems for datacom equipment in NTT
Author :
Aoki, Tadahito ; Yamasaki, Mikio ; Takeda, Takashi ; Tanaka, Toru ; Harada, Hideki ; Nakamura, Kimio
Author_Institution :
NTT Energy & Environ. Syst. Labs., Tokyo, Japan
Abstract :
This paper describes the guidelines for power-supply systems for datacom equipment in NTT that were established at the beginning of 2002, to prevent accidents in power-supply systems. The guidelines indicate that the -48 VDC power-supply system is preferable for supplying power to the datacom equipment. They specify that the input capacitor in a DC-DC converter used in datacom equipment should have a value of at least 0.3 μF/W and that a capacitor should be connected to the input of the power distribution frame to prevent the oscillation in a -48 VDC system. They also prescribe that a pre-charge circuit should be installed to prevent inrush current to datacom equipment. If power-supply systems for datacom equipment follow these guidelines, there will be fewer serious accidents.
Keywords :
DC-DC power convertors; capacitors; power supplies to apparatus; power system protection; telecommunication power supplies; -48 V; DC-DC converter; NTT; accidents prevention; capacitor; datacom equipment; input capacitor; inrush current prevention; oscillation prevention; power distribution frame; power-supply system; power-supply systems; pre-charge circuit; AC generators; Batteries; Engines; Guidelines; IP networks; Power generation; Power supplies; Power system reliability; Rectifiers; Uninterruptible power systems;
Conference_Titel :
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN :
0-7803-7512-2
DOI :
10.1109/INTLEC.2002.1048646