DocumentCode
2470538
Title
Experimental evaluation of space vector oriented active DC-side current balancing of two parallel connected three-phase three-switch buck-type unity power factor rectifier systems
Author
Baumann, Martha ; Kolar, Joham W.
Author_Institution
Inst. of Electr. Drives & Machines, Vienna Univ. of Technol., Austria
fYear
2002
fDate
2002
Firstpage
317
Lastpage
324
Abstract
In this paper the parallel connection of two three phase buck-type unity power factor rectifier systems is investigated experimentally for a 10 kW DSP-controlled prototype. There, a space vector modulation scheme is employed which shows all advantages of interleaved operation of the two systems. Three control schemes for active DC-side current balancing are described. The control schemes do differ concerning their control action and concerning additional switching losses. All control structures discussed in this paper are based on employing an additional free-wheeling states which do allow influence of the rate of change of the DC-side currents and can therefore be used for DC-side current balancing.
Keywords
digital control; digital signal processing chips; electric current control; losses; power factor; rectifying circuits; switching convertors; 10 kW; DSP-controlled prototype; control action; control structures; free-wheeling states; interleaved operation; parallel connected rectifier systems; space vector modulation scheme; space vector oriented active DC-side current balancing; switching losses; three-phase three-switch buck-type rectifier systems; unity power factor rectifier systems; Frequency; Laboratories; Power electronics; Power harmonic filters; Prototypes; Pulse width modulation; Reactive power; Rectifiers; Switches; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN
0-7803-7512-2
Type
conf
DOI
10.1109/INTLEC.2002.1048674
Filename
1048674
Link To Document