DocumentCode
2472071
Title
Novel algorithm for earth-fault location in compensated MV-networks
Author
Altonen, Janne ; Wahlroos, Ari
Author_Institution
ABB Oy Medium Voltage Products, Helsinki, Finland
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
This paper presents a novel earth-fault location algorithm, which enables the estimation of the earth-fault distance in compensated MV-networks. The novelty of the algorithm is that the fault location can be calculated with reduced number of settings compared to prior-art methods. This improves the practical usability and accuracy of the earth-fault location. The key idea of the novel algorithm is to provide a set of equations based on an equivalent circuit valid for single-phase earth fault so that for the first time four unknown variables can be determined, that is, the fault distance and fault resistance, but also the conductance and susceptance parts of the shunt admittance of the protected line. Until now it has been mandatory to give the shunt admittance value of the protected line as a setting to enable impedance based fault location computation in compensated MV-networks. With the suggested algorithm the earth-fault distance can be estimated without setting the shunt admittance value, although its influence is included in the method. In the paper, the basic theory of modeling the phase-to-earth fault loop and the challenges related to it are shortly reviewed first. Secondly, the theory of the novel algorithm is introduced. Finally, the performance of the novel algorithm is compared to one of the prior-art solutions. This is done using data from comprehensive field tests conducted in a typical rural 20 kV overhead line network with central compensation. The results clearly demonstrate the significance of the shunt admittance parameter in providing meaningful results when the prior-art methods are used. The results also show that the novel algorithm extends the application of computational fault location in terms of fault resistance from solid earth faults into low-impedance earth faults. However, the practicall
Keywords
electric admittance; fault location; power distribution faults; power distribution lines; power engineering computing; IED; compensated MV-networks; conductance; earth-fault distance; equivalent circuit; fault location computation; fault resistance; low-impedance earth faults; measurement transformers; novel earth-fault location algorithm; overhead line network; phase-to-earth fault loop; shunt admittance value; single-phase earth fault; solid earth faults; susceptance; voltage 20 kV;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location
Stockholm
Electronic_ISBN
978-1-84919-732-8
Type
conf
DOI
10.1049/cp.2013.0832
Filename
6683435