DocumentCode
2472954
Title
The frequency effect of HV and electroluminescence in XLPE
Author
Cissé, L. ; Bamji, S.S. ; Bulinski, A.T.
Author_Institution
Nat. Res. Council of Canada, Ottawa, Ont., Canada
fYear
2002
fDate
2002
Firstpage
283
Lastpage
286
Abstract
The frequency effect of the ac voltage used for on-site diagnostic tests of underground HV cables is determined with the Electroluminescence (EL) technique. HV up to 28 kV at frequencies from 30 to 600 Hz is applied to semicon tips embedded in cross-linked polyethylene (XLPE). The number of EL pulses detected by a photomultiplier and the area of the space charge region, simultaneously obtained by the CCD camera, are studied. The implications of the frequency range on diagnostic tests performed on the polymeric insulation of underground power cables are discussed.
Keywords
XLPE insulation; electroluminescence; insulation testing; power cable insulation; power cable testing; space charge; underground cables; 28 kV; 30 to 600 Hz; AC voltage; CCD camera; XLPE; cross-linked polyethylene; electroluminescence; frequency dependence; on-site diagnostic HV test; photomultiplier; polymeric insulation; semicon tip; space charge; underground power cable; Cables; Charge coupled devices; Charge-coupled image sensors; Electroluminescence; Frequency; Photomultipliers; Polyethylene; Space charge; Testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN
0-7803-7502-5
Type
conf
DOI
10.1109/CEIDP.2002.1048790
Filename
1048790