DocumentCode
2473698
Title
Aging diagnosis of solid insulation for large oil-immersed power transformers
Author
Dong, M. ; Shang, Y. ; Zhao, W.B. ; Yan, Z. ; Zheng, Z.
Author_Institution
Sch. of Electr. Eng., Xi´´an Jiaotong Univ., China
fYear
2002
fDate
2002
Firstpage
400
Lastpage
403
Abstract
Furfural analysis has been proved a useful tool for the aging diagnosis of solid insulation in large oil-immersed power transformers. Up-to-now, diagnostic criteria for operating transformers are in urgent need. In the investigation, quite a lot of data have been collected, such as the furfural concentrations, service durations, water contents, etc. To reveal the relationship between furfural contents in oil and the aging condition of solid insulation, statistic analyses are carried out. Then, the factors affecting the aging process such as service duration is studied. Therefore, the statistic distribution of furfural concentration in oil is worked out. According to the theoretical distribution, several warning levels of furfaral in oil could be calculated, which are more reasonable than that the regulation had recommended. An example of practical application shows it is effective and easy to apply for operating transformers.
Keywords
ageing; power transformer insulation; aging diagnosis; diagnostic criteria; furfural concentrations; large oil-immersed power transformers; service durations; solid insulation; water contents; Aging; Insulation testing; Oil insulation; Petroleum; Plastic insulation; Power transformer insulation; Power transformers; Solids; Statistical analysis; Statistical distributions;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN
0-7803-7502-5
Type
conf
DOI
10.1109/CEIDP.2002.1048819
Filename
1048819