Title :
On-line partial discharge diagnosis on large motors
Author :
Gross, Detlev W.
Author_Institution :
Power Diagnostix Syst. GmbH, Aachen, Germany
Abstract :
The typical epoxy-mica insulation system of large motors is a ´forgiving´ insulation system. Thus, besides showing mere electrical problems, partial discharge activity further serves as an indicator for other defect mechanisms, such as of mechanical, thermal, or environmental influence. On-line partial discharge diagnosis on large motors is greatly simplified when permanent partial discharge signal couplers are installed. Different cost-effective coupling techniques, such as Rogowski coils or coupling capacitors are discussed. Several examples for the analysis of high-resolution phase resolved partial discharge pattern and the related defect mechanism are discussed. Continuous on-line monitoring of the discharge activity can be advantageous to achieve extended maintenance intervals.
Keywords :
electric motors; epoxy insulation; machine insulation; maintenance engineering; partial discharge measurement; Rogowski coils; coupling capacitors; epoxy-mica insulation; large motors; maintenance intervals; on-line partial discharge diagnosis; permanent partial discharge signal couplers; Couplers; Couplings; Insulation; Job shop scheduling; Partial discharge measurement; Partial discharges; Pollution measurement; Signal resolution; Vibration measurement; Voltage;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN :
0-7803-7502-5
DOI :
10.1109/CEIDP.2002.1048837