DocumentCode :
2475537
Title :
Extruded insulated cable deterioration mechanism and PD
Author :
Ahmed, Nezar ; Srinivas, Nagu
Author_Institution :
DTE Energy Technol. Inc., Farmington Hill, MI, USA
fYear :
2002
fDate :
2002
Firstpage :
744
Lastpage :
747
Abstract :
The electrical strengths of the dielectrics used in extruded power cables and accessories are far higher than the stresses these devices encounter in their life span. Failures of these devices are associated with imperfections and foreign substances introduced during manufacturing processes, shipping, installation and also during the operation of these components (aging). In this paper, the relationship between such imperfections or aging processes and PD is discussed.
Keywords :
partial discharges; power cable insulation; trees (electrical); aging; electrical strength; electrical stress; electrical trees; extruded power cables; foreign substances; imperfections; metallic contamination; partial discharges; water trees; Aging; Cable insulation; Dielectrics and electrical insulation; Electrodes; Electrons; Partial discharges; Polymers; Power cables; Thermal stresses; Trees - insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN :
0-7803-7502-5
Type :
conf
DOI :
10.1109/CEIDP.2002.1048903
Filename :
1048903