  • Abstract
    The electric field and voltage distributions along wet polymer insulators are calculated using COULOMB, a three-dimensional electric field analysis software package. These distributions are distorted by the presence of water droplets on the surface of the insulators. The cases analyzed are based on several stages of the hydrophobicity classification (HC) recommended by the Swedish Transmission Research Institute (STRI). The models developed for the calculations are based on photographs of insulators undergoing aging tests in a fog chamber. The insulator surfaces of the cases selected for the calculations are characterized as HC1, HC2 and HC3. Electric field and equipotential lines and electric field enhancement factors on the surface of water droplets are presented.
  • Keywords
    electric fields; polymer insulators; voltage distribution; 3D electric field analysis software package; aging tests; electric field distribution; equipotential lines; field enhancement factors; polymer insulators; voltage distribution; water droplets; wet surface conditions; Aging; Computer aided software engineering; Corona; Dielectrics and electrical insulation; Plastic insulation; Polymers; Surface contamination; Surface discharges; Voltage; Water pollution;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
  • Print_ISBN
    0-7803-7502-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2002.1048926
  • Filename
    1048926