• DocumentCode
    2477332
  • Title

    Efficient immunity testing of smart meter devices in the frequency range 2–150 kHz

  • Author

    Gronwald, Frank ; Conrads, Ralf ; Janssen, Rick ; Weber, Thomas

  • Author_Institution
    Hamburg Univ. of Technol., Hamburg, Germany
  • fYear
    213
  • fDate
    10-13 June 213
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Energy networks are subject to considerable disturbing currents in the frequency range of 2-150 kHz, due to insufficient Electromagnetic Compatibility standards, and it is important that smart meter devices exhibit in this frequency range sufficient immunity. It is shown that corresponding immunity tests in frequency domain must utilize small enough frequency spacing since smart meter susceptibilities can be rather narrowband, as is shown by example. It is also pointed out that for efficient testing the use of broadband test pulses provides advantages if compared to single frequency sweeps.
  • Keywords
    electromagnetic compatibility; frequency-domain analysis; immunity testing; smart meters; broadband test pulses; electromagnetic compatibility standards; energy networks; frequency 2 kHz to 150 kHz; frequency domain; immunity testing; smart meter devices; smart meter susceptibilities;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
  • Conference_Location
    Stockholm
  • Electronic_ISBN
    978-1-84919-732-8
  • Type

    conf

  • DOI
    10.1049/cp.2013.1081
  • Filename
    6683684