Title
Detection of single phase earth fault in compensated network with C0 estimation
Author
Loos, Matthieu ; Werben, Stefan ; Kereit, Matthias ; Maun, Jean-Claude
Author_Institution
Univ. Libre de Bruxelles, Brussels, Belgium
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
Single phase earth fault in compensated network creates faulty current with very small magnitude. The connection of a Petersen Coil in the transformer neutral turns the zero sequence impedance into very high ohmic system. The small faulty current makes the detection of the faulty feeder impossible with simple over current protection. That is why algorithms are using transients. This paper presents a novel method to detect such earth fault with a strong sensitivity regarding the fault impedance. The algorithm builds a model of the sound feeder behaviour using the zero sequence voltage and current. The healthy feeder can be considered as a zero sequence capacitance. By measuring the deviation of a perfectly capacitive feeder, the faulty one can be detected. Algorithm description and tests are presented with comparison of small impedance fault and high impedance with recordings and simulations.
Keywords
fault diagnosis; overcurrent protection; power distribution faults; power distribution protection; power transformers; Petersen coil; capacitive feeder; compensated network; fault impedance; faulty current; faulty feeder; healthy feeder; overcurrent protection; single phase earth fault detection; sound feeder behaviour; transformer neutral; zero sequence capacitance; zero sequence current; zero sequence voltage;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location
Stockholm
Electronic_ISBN
978-1-84919-732-8
Type
conf
DOI
10.1049/cp.2013.1120
Filename
6683723