• DocumentCode
    2478106
  • Title

    Detection of single phase earth fault in compensated network with C0 estimation

  • Author

    Loos, Matthieu ; Werben, Stefan ; Kereit, Matthias ; Maun, Jean-Claude

  • Author_Institution
    Univ. Libre de Bruxelles, Brussels, Belgium
  • fYear
    213
  • fDate
    10-13 June 213
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Single phase earth fault in compensated network creates faulty current with very small magnitude. The connection of a Petersen Coil in the transformer neutral turns the zero sequence impedance into very high ohmic system. The small faulty current makes the detection of the faulty feeder impossible with simple over current protection. That is why algorithms are using transients. This paper presents a novel method to detect such earth fault with a strong sensitivity regarding the fault impedance. The algorithm builds a model of the sound feeder behaviour using the zero sequence voltage and current. The healthy feeder can be considered as a zero sequence capacitance. By measuring the deviation of a perfectly capacitive feeder, the faulty one can be detected. Algorithm description and tests are presented with comparison of small impedance fault and high impedance with recordings and simulations.
  • Keywords
    fault diagnosis; overcurrent protection; power distribution faults; power distribution protection; power transformers; Petersen coil; capacitive feeder; compensated network; fault impedance; faulty current; faulty feeder; healthy feeder; overcurrent protection; single phase earth fault detection; sound feeder behaviour; transformer neutral; zero sequence capacitance; zero sequence current; zero sequence voltage;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
  • Conference_Location
    Stockholm
  • Electronic_ISBN
    978-1-84919-732-8
  • Type

    conf

  • DOI
    10.1049/cp.2013.1120
  • Filename
    6683723