DocumentCode
2478898
Title
Innovative and safe cable connection in medium voltage switchgear with integrated earthing and testing facilities
Author
Pikkert, Alex ; Binnendijk, Martin ; Van Riet, Maarten ; Harmsen, Denny
Author_Institution
Eaton, Hengelo, Netherlands
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
In networks operating at 24kV, fully enclosed and earthed cable connectors described in EN 50181 are widely used for connecting medium voltage cables to compact switchgear. During installation, and sometimes during the service life, it is necessary to remove, change or repair those connectors. Of course safety procedures are followed prior to cable access to avoid any dangerous situation. However, the full insulation combined with an earthed layer is a complicating factor for transparent access procedures. In The Netherlands where traditionally the majority of the MV networks operate at 12kV, cable connections with more easy access are in use since many years, enabling more obvious earthing and access procedures. This is of vital importance for field personnel, whose safety depends on it. In this paper we propose a new innovative cable connection that offers the unambiguous safety functionality up to and including 24kV, whereas this was only possible for 12kV until now. We describe the new insulated, non-earthed cable connection with integrated earthing and test facility, and the design process including laboratory testing up to first introduction. Furthermore, we provide a complete modern approach for interconnecting Ring Main Units (RMU´s). This includes 3-phase network cables to minimize magnetic fields, special joints from 1-to 3-phase cables to connect to the RMU, an earthing method preventing significant induction currents and the innovative, crystal clear safety procedures.
Keywords
earthing; power cables; safety; switchgear protection; 1-phase cables; 3-phase cables; MV networks; Netherlands; RMU; cable connections; crystal clear safety procedures; earthed cable connectors; earthed layer; field personnel; fully enclosed cable connectors; innovative cable connection; integrated earthing; magnetic fields; medium voltage cables; medium voltage switchgear; nonearthed cable connection; ring main units; safe cable connection; service life; testing facilities; transparent access procedures; voltage 12 kV; voltage 24 kV;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location
Stockholm
Electronic_ISBN
978-1-84919-732-8
Type
conf
DOI
10.1049/cp.2013.1160
Filename
6683763
Link To Document