• DocumentCode
    2478898
  • Title

    Innovative and safe cable connection in medium voltage switchgear with integrated earthing and testing facilities

  • Author

    Pikkert, Alex ; Binnendijk, Martin ; Van Riet, Maarten ; Harmsen, Denny

  • Author_Institution
    Eaton, Hengelo, Netherlands
  • fYear
    213
  • fDate
    10-13 June 213
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    In networks operating at 24kV, fully enclosed and earthed cable connectors described in EN 50181 are widely used for connecting medium voltage cables to compact switchgear. During installation, and sometimes during the service life, it is necessary to remove, change or repair those connectors. Of course safety procedures are followed prior to cable access to avoid any dangerous situation. However, the full insulation combined with an earthed layer is a complicating factor for transparent access procedures. In The Netherlands where traditionally the majority of the MV networks operate at 12kV, cable connections with more easy access are in use since many years, enabling more obvious earthing and access procedures. This is of vital importance for field personnel, whose safety depends on it. In this paper we propose a new innovative cable connection that offers the unambiguous safety functionality up to and including 24kV, whereas this was only possible for 12kV until now. We describe the new insulated, non-earthed cable connection with integrated earthing and test facility, and the design process including laboratory testing up to first introduction. Furthermore, we provide a complete modern approach for interconnecting Ring Main Units (RMU´s). This includes 3-phase network cables to minimize magnetic fields, special joints from 1-to 3-phase cables to connect to the RMU, an earthing method preventing significant induction currents and the innovative, crystal clear safety procedures.
  • Keywords
    earthing; power cables; safety; switchgear protection; 1-phase cables; 3-phase cables; MV networks; Netherlands; RMU; cable connections; crystal clear safety procedures; earthed cable connectors; earthed layer; field personnel; fully enclosed cable connectors; innovative cable connection; integrated earthing; magnetic fields; medium voltage cables; medium voltage switchgear; nonearthed cable connection; ring main units; safe cable connection; service life; testing facilities; transparent access procedures; voltage 12 kV; voltage 24 kV;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
  • Conference_Location
    Stockholm
  • Electronic_ISBN
    978-1-84919-732-8
  • Type

    conf

  • DOI
    10.1049/cp.2013.1160
  • Filename
    6683763