Title :
Intelligent control and power management of air conditioning systems using fuzzy logic and local operation networks
Author :
Talebi-Daryani, R. ; Pfaff, Jan
Author_Institution :
Univ. of Appl. Sci. Cologne, Germany
Abstract :
Use of fuzzy logic control (FLC) system in combination with LON ( Local Operation NetworkR) - technology for control and power management of air conditioning (AC) systems increases the exchange of control information of the system. Instead of using one actuator (usually control valve) in common control strategy for temperature control, we use now two actuators (valve and pump) for optimal control of a supply temperature of an AC system. Using variable speed operated pumps for the heat exchangers reduces enormously the electrical power consumption of the pump during the control mode of the system. The control information exchange system provided by LON works ensures that only one of the actuators executes the control task within the scan time cycle, which is important for robust control. Based on the experience of using FC system for non linear AC- systems, two fuzzy controllers for valve and variable speed control of the pump provides best results for the quality of a supply air temperature control loop and power management for control pumps.
Keywords :
actuators; air conditioning; fuzzy control; intelligent control; optimal control; power consumption; robust control; temperature control; actuator; air conditioning systems; control pumps; fuzzy controllers; fuzzy logic; heat exchangers; intelligent control; local operation networks; optimal control; power management; robust control; temperature control; variable speed control; variable speed operated pumps; Actuators; Air conditioning; Control systems; Electric variables control; Energy management; Fuzzy logic; Intelligent control; Optimal control; Power system management; Temperature control;
Conference_Titel :
Automation Congress, 2002 Proceedings of the 5th Biannual World
Print_ISBN :
1-889335-18-5
DOI :
10.1109/WAC.2002.1049442