Abstract :
In this paper, the authors present measurements taken while a mini hydro power plant and its adjoining load were islanded on a 25 kV distribution feeder. This was part of the acceptance tests carried out before commissioning. The frequency was allowed to vary from 56.3 to 64.5 Hz before the generation was tripped off. The authors also present the estimation of the moment of inertia of the generating system from these measurements
Keywords :
distribution networks; hydroelectric power stations; power system measurement; 25 kV; 56.3 to 64.5 Hz; acceptance tests; distribution feeder; hydropower generation; islanding tests; measurements; mini hydro generating plant; moment of inertia; Frequency; Performance evaluation; Power generation; Power measurement; Power system modeling; Power system reliability; Power system stability; Power system transients; Testing; Voltage;