DocumentCode :
2484363
Title :
NEC grounding requirements for parallel circuits
Author :
Daly, James M.
Author_Institution :
BICC Cables Corp., West Nyack, NY, USA
fYear :
1996
fDate :
6-9 May 1996
Firstpage :
173
Lastpage :
176
Abstract :
The 1996 National Electrical Code requires that the equipment grounding conductor must be run in parallel when the circuit conductors are run in parallel and be sized on the basis of the ampere rating of the overcurrent protective device. This paper reviews the requirements for parallel circuits, the specific requirements for parallel equipment grounding conductors and the methods of complying with the NEC. Open wiring raceway, cable tray, direct burial and underground duct installations as normally utilized in an industrial facility are addressed; other wiring methods that are more commonly used in commercial applications are not included
Keywords :
conductors (electric); earthing; electric conduits; industrial plants; industrial power systems; overcurrent protection; power cables; standards; underground cables; underground distribution systems; 1996 National Electrical Code; NEC grounding requirements; cable tray; circuit conductors; direct burial; equipment grounding conductor; industrial facility; open wiring raceway; overcurrent protective device; parallel circuits; parallel equipment grounding conductors; underground duct; wiring methods; Aluminum; Circuits; Conducting materials; Conductors; Copper; Grounding; National electric code; Protection; Underground power cables; Wiring;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 1996. Conference Record, Papers Presented at the 1996 Annual Meeting., IEEE 1996
Conference_Location :
New Orleans, LA
Print_ISBN :
0-7803-3263-6
Type :
conf
DOI :
10.1109/ICPS.1996.533952