Title :
Evaluating generator breakers short-circuit duty using IEEE Std. C37.010 and C37.013
Author :
Dartawan, Ketut ; Pierre, Conrad St
Author_Institution :
Pterra Consulting, Albany, NY, USA
Abstract :
This paper describes a procedure for calculating generator circuit breaker duty. Presently, commercially available software products help in determining the duty for a general purpose circuit breaker. However, further calculations are needed to determine the duty for a special purpose generator circuit breaker. IEEE Std C37.010-1999 (Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis) provides the calculation procedure for general-purpose circuit breakers. This paper presents a procedure to evaluate a special purpose generator-circuit breaker, providing a duty multiplication factor based on the test X/R ratio of generator breakers given in IEEE Std C37.013 (Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis).
Keywords :
IEEE standards; circuit breakers; machine protection; short-circuit currents; synchronous generators; AC generators; AC high-voltage generator circuit breakers; C37.013; IEEE Std C37.010-1999; duty multiplication factor; generator circuit breaker short-circuit duty evaluation; software products; special purpose generator circuit breaker; symmetrical current basis; synchronous generators; test X/R ratio; Generators; Reactive power; Resistance; AC generators; Circuit breakers; IEC Standards; IEEE Standards; Interrupters; Synchronous Generators;
Conference_Titel :
Industrial & Commercial Power Systems Technical Conference (I&CPS), 2012 IEEE/IAS 48th
Conference_Location :
Louisville, KY
Print_ISBN :
978-1-4673-0652-2
DOI :
10.1109/ICPS.2012.6229619