DocumentCode
2498025
Title
Performance analysis of shunt active power filter using PLL based control algorithms under distorted supply condition
Author
Patjoshi, R.K. ; Mahapatra, Kamala Kanta
Author_Institution
Dept. of Electron. & Commun. Eng., Nat. Inst. of Technol., Rourkela, India
fYear
2013
fDate
12-14 April 2013
Firstpage
1
Lastpage
6
Abstract
This paper presents three different PLL based control algorithms for shunt active Power filter (SAPF) under the distorted supply condition. Different synchronisation techniques such as Modified SRF (MSRF-PLL), Transformation angle detector and SRF based PLL have been applied to SAPF and analyzed under different distortion conditions of supply voltage. From the simulation results, it is found that the MSRF-PLL achieves better performance as compared to other two standard PLL techniques on the basis of THD% (total harmonic distortion). The MSRF-PLL is fast in transient response and robust against disturbances on the grid voltage wave. Here simulation has been carried out using MATLAB under distorted line voltage conditions.
Keywords
active filters; distortion; harmonic distortion; phase locked loops; power filters; MSRF-PLL; Matlab; PLL-based control algorithms; SAPF; distorted line voltage conditions; distorted supply condition; distortion conditions; grid voltage wave; shunt active power filter performance analysis; synchronisation techniques; transient response; Active filters; Detectors; Harmonic analysis; Oscillators; Phase locked loops; Power harmonic filters; Synchronization; Angle Detector SRF; Modified SRF; SRF PLL; distorted line voltage; harmonic distortion;
fLanguage
English
Publisher
ieee
Conference_Titel
Engineering and Systems (SCES), 2013 Students Conference on
Conference_Location
Allahabad
Print_ISBN
978-1-4673-5628-2
Type
conf
DOI
10.1109/SCES.2013.6547523
Filename
6547523
Link To Document