Partial discharge testing of motor and generator windings: an absolute or a comparison test?
Author
Stone, Greg C. ; Kantardziski, Peter
Author_Institution
Iris Power Eng. Inc., Etobicoke, Ont., Canada
fYear
1998
fDate
27-30 Sep 1998
Firstpage
63
Lastpage
66
Abstract
Partial discharge (PD) tests on operating motors and generators are now widely used around the world to assess the condition of the stator winding insulation. Data is presented which shows that the calibration into picoCoulumbs can yield misleading interpretations. The reasons for this are discussed. The conclusion is that with present technology, PD testing of stator windings can only be comparative
Keywords
calibration; insulation testing; machine insulation; machine testing; partial discharge measurement; stators; calibration; generator; motor; partial discharge testing; stator winding insulation; Antenna measurements; Capacitance measurement; Electric variables measurement; Electrons; Frequency; Insulation testing; Partial discharges; Power transformer insulation; Pulse measurements; Stator windings;