• DocumentCode
    2498515
  • Title

    A protection and fault location scheme for EHV line with series capacitor based on travelling waves and wavelet analysis

  • Author

    Huang, Zijun ; Chen, Yunping ; Gong, Qingwu

  • Author_Institution
    Sch. of Electr. Eng., Wuhan Univ., Hubei, China
  • Volume
    1
  • fYear
    2002
  • fDate
    13-17 Oct 2002
  • Firstpage
    290
  • Abstract
    A scheme based on wavelet for construction of the fast protection and fault location for series compensation is described in this paper. Current travelling waves, which are more easily captured than voltage waves, are used and decomposed into mode components. The line mode component is represented by its wavelet modulus maxima. The incident and reflection travelling waves are identified by analyzing the amplitudes and polarities of their wavelet modulus maxima. The interval between incident and reflection travelling waves reveals the fault position. EMTP simulations proved that the scheme is correct and effective.
  • Keywords
    EMTP; fault location; power capacitors; power system analysis computing; power transmission faults; power transmission lines; power transmission protection; wavelet transforms; EHV transmission lines; EMTP; computer simulation; current travelling waves; fast protection; fault location; incident waves; line mode components; series compensation; wavelet analysis; wavelet modulus maxima; Capacitors; Fault location; Impedance; Power system protection; Power system transients; Power transmission lines; Protective relaying; Reflection; Wavelet analysis; Wavelet transforms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
  • Print_ISBN
    0-7803-7459-2
  • Type

    conf

  • DOI
    10.1109/ICPST.2002.1053551
  • Filename
    1053551