Abstract
This paper presents an effective algorithm to locate Single Line to Ground (SLG) fault at a transmission line. Post fault voltages and currents from both substation terminals were used as the input parameters to the algorithm. Discrete Fourier Transform (DFT) was used to extract the magnitudes and phase angles of three phase voltages and currents. The modeling of the transmission line along with the algorithm was performed using Matlab/Simulink package. The results of fault location for SLG faults along the transmission line demonstrated the validity of the algorithm used even for high resistance earth fault.
Keywords
discrete Fourier transforms; earthing; fault location; power transmission faults; power transmission lines; power transmission protection; substation protection; DFT; Matlab-Simulink package; SLG fault; discrete Fourier transform; high-resistance earth fault; post-fault current; post-fault voltage; substation terminals; three-phase current; three-phase voltage; transmission line; two-terminal single-line-to-ground fault location algorithm; Circuit faults; Estimation; Fault location; Mathematical model; Power transmission lines; Resistance; Substations; Discrete Fourier Transform; Fault Location; Matlab/Simulink; Single Line to Ground; Two-terminal;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering and Optimization Conference (PEDCO) Melaka, Malaysia, 2012 Ieee International
Conference_Location
Melaka
Print_ISBN
978-1-4673-0660-7
Type
conf
DOI
10.1109/PEOCO.2012.6230869
Filename
6230869
Link To Document